12:00 2021-10-07
Spoke w/Surat Singh: Johnson controls Contract.

Notes in invoice dated 2021-04-10
Ref: 29108-WA32722

Site visit 2020-04-10
Contact: Matt Hansen, Manager

FSS Inspector Heath Dangerfield
Scope of work:  Went to job site to service system
 - Cot there and it had just been done by Johnson Controls Mar-23, 2020
 - Noticed the dry system was shut down								
 - Noticed the air compressor had just been replaced with a new DeWalt air compressor								
 - The new compressor was not plugged in to the wall
 - It is not mounted to the floor
 - It does not have LISTING TO BE ON A FIRE PROTECTION DRY SYSTEM
 - We the reset the Dry-System Clapper valve
 - Repressurised the system
 - ADJUSTED THE PRESSURE and left the system in service 								

NOTE: A UL RATED - FM LISTED AIR compressor NEEDS TO								
BE INSTALLED